Drive Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp

Terminal

Model

Number

Tool

Insulation

Cap Model

No.

Code

<1>

R/L1, S/L2, T/L3 U/T1, V/T2, W/T3

Machine No.

Die Jaw

4A0414

4/0 × 2P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 2P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 2P

4A0515

3/0 × 4P

3/0 × 4P

M12

80-L12

YF-1

YET-300-1

TD-323,

TD-312

TP-080

100-051-558

4/0 × 4P

4/0 × 4P

100-L12

TD-324,

TD-312

TP-100

100-051-560

250 × 4P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 2P

4A0675

4/0 × 4P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 4P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 4P

4A0930

3/0 × 8P

M12

80-L12

YF-1

YET-300-1

TD-323,

TD-312

TP-080

100-051-558

4/0 × 8P

100-L12

TD-324,

TD-312

TP-100

100-051-560

250 × 8P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 8P

4A1200

4/0 × 8P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 8P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 8P

<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.

Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].

Note:

Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable

temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.

Factory Recommended Branch Circuit Protection for UL Compliance

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.

Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral

devices if the cause cannot be identified.

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in the tables

below.

Table C.7 Factory Recommended A1000 AC Drive Branch Circuit Protection (Normal Duty)

Drive Model

A1000 in Normal Duty Mode (C6-01 = 1)

Nominal

Output Power

HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay Fuse

Rating Amps

<2>

Non-time Delay

Fuse Rating

Amps

<3>

Bussman Semi-

conductor Fuse

Rating (Fuse

Ampere)

<4>

200 V Class

2A0004

0.75

3.9

15

6.25

10

FWH-70B (70)

2A0006

1 - 1.5

7.3

15

12

20

FWH-70B (70)

2A0008

2

8.8

15

15

25

FWH-70B (70)

2A0010

3

10.8

20

17.5

30

FWH-70B (70)

2A0012

3

13.9

25

20

40

FWH-70B (70)

2A0018

5

18.5

35

30

50

FWH-90B (90)

2A0021

7.5

24

45

40

70

FWH-90B (90)

C.2 UL and CSA Standards

360

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide