No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-47

<5>

(017D)

Reverse Operation

Selection 2 by PID

Output

Output Rev Sel2

0: 0 limit

1: Reverse

Reverse operation selection when b5-01 = 3 or 4.

0: Zero limit when PID output is a negative value.

1: Reverse operation when PID output is a negative value

(Zero limit if the reverse operation is prohibited by b1-04).

Default: 1

Range: 0, 1

<1> Default setting is determined by parameter o2-04, Drive Model Selection.
<2> Settings 5 to 8 are available in drive software versions PRG: 1019 and later.
<3> Default setting is determined by parameter A1-02, Control Method Selection.
<4> Default setting is determined by parameter b5-20, PID Setpoint Scaling.
<5> Available in drive software versions PRG: 1015 and later.

u

b6: Dwell Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b6-01

(01B6) Dwell Reference at Start Dwell Ref @Start

Parameters b6-01 and b6-02 set the frequency to hold and the

time to maintain that frequency at start.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b6-02

(01B7) Dwell Time at Start

Dwell Time@Start

Default: 0.0 s

Min.: 0.0

Max.: 10.0

b6-03

(01B8) Dwell Reference at Stop Dwell Ref @Stop

Parameters b6-03 and b6-04 set the frequency to hold and the

time to maintain that frequency at stop.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b6-04

(01B9) Dwell Time at Stop

Dwell Time @Stop

Default: 0.0 s

Min.: 0.0

Max.: 10.0

u

b7: Droop Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b7-01

(01CA) Droop Control Gain

DROOP Quantity

Sets the speed reduction gain applied at a torque reference of

100%. Set as a percentage of motor base speed.

Default: 0.0%

Min.: 0.0

Max.: 100.0

b7-02

(01CB) Droop Control Delay

Time

DROOP Delay Time

Adjusts the responsiveness of Droop Control.

Default: 0.05 s

Min.: 0.03

Max.: 2.00

b7-03

(017E)

<1>

Droop Control Limit

Selection

Droop Limit Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

<1> Available in drive software versions PRG: 1015 and later.

u

b8: Energy Saving

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b8-01

(01CC)

Energy Saving Control

Selection

Energy Save Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default:

<1>

Range: 0, 1

b8-02

(01CD) Energy Saving Gain

Energy Save Gain

Sets the gain used for Energy Saving.

Default:

<1>

Min.: 0.0

Max.: 10.0

b8-03

(01CE) Energy Saving Control

Filter Time Constant

Energy Save F.T

Sets a time constant for Energy Saving.

Default:

<2>

Min.: 0.00 s

Max.: 10.00 s

B.2 b: Application

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

273

B

Parameter List