(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C5-38

(0279)

Motor 2 Load Inertia

Ratio

Load Inertia 2

Sets the ratio between the motor 2 and machine inertia. This

value is automatically set during ASR or Inertia Auto-Tuning.

Default: 1.0

Min.: 0.0

Max.: 6000.0

C5-39

(030D)

ASR Primary Delay

Time Constant 2

ASR Delay Time 2

Sets the filter time constant in seconds for the time from the

speed loop to the torque reference output when the Power KEB

Ride-Thru is enabled (L2-29 = 1).

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 0.000 s

Min.: 0.000

Max.: 0.500

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> The setting range is 1.00 to 300.00 in CLV and AOLV/PM control modes.
<3> Default setting is dependent on parameter E5-01, Motor Code Selection.
<4> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<5> Default setting is determined by parameter E3-01, Motor 2 Control Mode Selection.

u

C6: Carrier Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C6-01

(0223)

Drive Duty Selection

Heavy/NormalDuty

0: Heavy Duty

1: Normal Duty

0: Heavy Duty (HD)

Overload capability: 150% of drive rated Heavy Duty current

for 60 s

Default Carrier Frequency: 2 kHz

1: Normal Duty (ND)

Overload capability: 120% of drive rated Normal Duty current

for 60 s

Default Carrier Frequency: 2 kHz Swing PWM

Default: 1

Range: 0, 1

167

C6-02

(0224)

Carrier Frequency

Selection

CarrierFreq Sel

1: Fc=2.0 kHz

2: Fc=5.0 kHz

3: Fc=8.0 kHz

4: Fc=10.0 kHz

5: Fc=12.5 kHz

6: Fc=15.0 kHz

7: Swing PWM1

8: Swing PWM2

9: Swing PWM3

A: Swing PWM4

F: Program

1: 2.0 kHz

2: 5.0 kHz (4.0 kHz)

3: 8.0 kHz (6.0 kHz)

4: 10.0 kHz (8.0 kHz)

5: 12.5 kHz (10.0 kHz)

6: 15.0 kHz (12.0 kHz)

7: Swing PWM1 (Audible sound 1)

8: Swing PWM2 (Audible sound 2)

9: Swing PWM3 (Audible sound 3)

A: Swing PWM4 (Audible sound 4)

B to E: No setting possible

F: User-defined (determined by C6-03 through C6-05)

Note:

1. The available settings are 1, 2, and F for

models

4A0930 and 4A1200.

2. The value in parenthesis indicates the carrier

frequency for AOLV/PM.

Default:

<1>

Range: 1 to 9;

A, F

168

C6-03

(0225)

Carrier Frequency Upper

Limit

CarrierFreq Max

Note:

C6-04 and C6-05 are available only in V/f and

V/f w/PG control modes.

Determines the upper and lower limits for the carrier frequency.

In OLV, C6-03 determines the upper limit of the carrier

frequency.

Carrier Frequency

E1-04

Max Output

Frequency

Output Frequency

× (C6-05) × K

Output

Frequency

C6-03

C6-04

Note:

The setting range is 1.0 to 5.0 kHz for models

4A0515 to 4A1200.

Default:

<2>

Min.: 1.0 kHz

Max.: 15.0 kHz

C6-04

(0226)

Carrier Frequency

Lower Limit

CarrierFreq Min

Default:

<2>

Min.: 1.0 kHz

Max.: 15.0 kHz

C6-05

(0227)

Carrier Frequency

Proportional Gain

CarrierFreq Gain

Default:

<2>

Min.: 0

Max.: 99

B.3 C: Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

279