Subchart A-1: Simple Motor Setup Using V/f Control

Flowchart A1 in

Figure 4.5

describes simple motor setup for V/f Control, with or without PG feedback. V/f Control is suited

for more basic applications such as fans and pumps. This procedure illustrates Energy Savings and Speed Estimation Speed

Search.

Perform Stationary Auto-Tuning for
Stator Resistance (T1-01 = 2)

NO

YES

Energy Savings

(b8-01 = 1) or

Speed Estimation Speed Search

(b3-24 = 1) enabled

when b3-01 = 1

or L2-01 = 1,2 ?

Is the motor cable longer than

50 meters?

Return to

Flowchart

A

Perform Rotational
Auto-Tuning for V/f Control
(T1-01 = 3)

Is there a

PG encoder

on the motor?

Set or verify the V/f pattern settings E1-oo.

Enter the number of motor poles to E2-04 (or E4-04 for motor 2).

Set the PG speed feedback parameters (F1-).

Set or verify the V/f pattern
settings E1-oo.

NO

YES

YES

NO

Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.

Couple the load or machine to the motor.

Run the machine and check for desired operation.

From

Flowchart

A

Figure 4.5 Simple Motor Setup with Energy Savings or Speed Search

4.3 Start-Up Flowcharts

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide