Si-t3, si-w3) – Yaskawa CIMR-AU 200V Drives User Manual

Page 297

Advertising
background image

u

F6: Communication Option Card (SI-B3, SI-C3, SI-ES3, SI-ET3, SI-N3, SI-P3, SI-S3,
SI-T3, SI-W3)

Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for CC-Link, CANopen, DeviceNet, EtherCAT,

PROFINET, BACnet, LonWorks, PROFIBUS-DP, MECHATROLINK-II, and MECHATROLINK-III options. Other

parameters in the F6 group are used for communication-protocol-specific settings. For more details on a specific option card,

refer to the instruction manual for the option.

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F6-01

(03A2)

Communications Error

Operation Selection

Comm Bus Flt Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-02

(03A3)

External Fault from

Comm. Option

Detection Selection

EF0 Detection

0: Always Detected

1: Only During Run

0: Always detected.

1: Detection during run only.

Default: 0

Range: 0, 1

F6-03

(03A4)

External Fault from

Comm. Option

Operation Selection

EF0 Fault Action

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-04

(03A5)

bUS Error Detection

Time

BUS Err Det Time

Sets the delay time for error detection if a bus error occurs.

Default: 2.0 s

Min.: 0.0

Max.: 5.0

F6-06

(03A7)

Torque Reference/

Torque Limit Selection

from Comm. Option

Torq Ref/Lmt Sel

0: Disabled

1: Enabled

0: Disabled. Torque reference/limit from option board

disabled.

1: Enabled. Torque reference/limit from option board enabled.

Default: 0

Range: 0, 1

F6-07

(03A8)

Multi-Step Speed

Enable/Disable

Selection when NefRef/

ComRef is Selected

Fref PrioritySel

0: Net/Com REF

1: MultiStep Speed

0: Multi-step reference disabled (same as F7)

1: Multi-step reference enabled (same as V7)

Default: 0

Range: 0, 1

F6-08

(036A)

<1>

Reset Communication

Parameters

Com Prm Init Sel

0: Init Com Prms

1: No Init Com Prms

0: Communication-related parameters (F6-oo/F7-oo) are

not reset when the drive is initialized using A1-03.

1: Reset all communication-related parameters

(F6-oo/F7-oo) when the drive is initialized using A1-03.

Default: 0

Range: 0, 1

F6-10

(03B6) CC-Link Node Address CC-Link Node Add

Sets the node address if a CC-Link option is installed.

Default: 0

Min.: 0

Max.: 64

F6-11

(03B7)

CC-Link

Communication Speed

CC-Link Baud

0: 156 kbps

1: 625 kbps

2: 2.5 Mbps

3: 5 Mbps

4: 10 Mbps

0: 156 Kbps

1: 625 Kbps

2: 2.5 Mbps

3: 5 Mbps

4: 10 Mbps

Default: 0

Range: 0 to 4

F6-14

(03BB)

CC-Link bUS Error

Auto Reset

Bus Err Auto Rst

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

F6-20

(036B)

MECHATROLINK

Station Address

Station Address

Sets the station address when the MECHATROLINK option

has been installed.

Default: 21
Min.: 20

<2>

Max.: 3F

<2>

F6-21

(036C)

MECHATROLINK

Frame Size

Frame length

0: 32-byte

<3>

1: 17-byte

<3>

Default: 0

Range: 0, 1

F6-22

(036D)

MECHATROLINK

Link Speed

Link Speed

0: 10MHz

1: 4MHz

0: 10 Mbps

1: 4 Mbps

Default: 0

Range: 0, 1

F6-23

(036E)

MECHATROLINK

Monitor Selection (E)

Mon E register

Sets the MECHATROLINK monitor (E).

Default: 0

Min.: 0

Max.: FFFF

F6-24

(036F)

MECHATROLINK

Monitor Selection (F)

Mon F register

Sets the MECHATROLINK monitor (F).

Default: 0

Min.: 0

Max.: FFFF

B.6 F: Options

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

297

B