Notes on using analog inputs as Multi-Speed 1, 2, and 3:
Multi-Step Speed 1

Set b1-01 to 1 to set terminal A1 analog input to Multi-Step Speed 1.
Set b1-01 to 0 when setting d1-01, Frequency Reference 1, to Multi-Step Speed 1.

Multi-Step Speed 2

Set H3-06, Terminal A3 Function Selection, to 2 (Auxiliary Frequency Reference 1) when setting terminal A3 analog input

to Multi-Step Speed 2.
Set H3-06 to F (Through mode) when setting d1-02, Frequency Reference 2, to Multi-Step Speed 2.

Multi-Step Speed 3

Set H3-10, Terminal A2 Function Selection, to 3 (Auxiliary Frequency Reference 2) when setting terminal A2 analog input

to Multi-Step Speed 3.
Set H3-10 to F (Through mode) when setting d1-03, Frequency Reference 3, to Multi-Step Speed 3.
Set H3-09 to 0 and set DIP switch S1 on the control circuit terminal board to V (voltage) when inputting 0 to 10 V to terminal

A2 analog input.

Select the different speed references as shown in

Table 4.12

.

Figure 4.23

illustrates the multi-step speed selection.

Table 4.12 Multi-Step Speed Reference and Terminal Switch Combinations

Reference

Multi-Step

Speed

H1-oo = 3

Multi-Step

Speed 2

H1-oo = 4

Multi-Step

Speed 3

H1-oo = 5

Multi-Step

Speed 4

H1-oo = 32

Jog Reference

H1-oo = 6

Frequency Reference 1 (set in b1-01)

OFF

OFF

OFF

OFF

OFF

Frequency Reference 2

(d1-02 or input terminal A1, A2, A3)

ON

OFF

OFF

OFF

OFF

Frequency Reference 3

(d1-03 or input terminal A1, A2, A3)

OFF

ON

OFF

OFF

OFF

Frequency Reference 4 (d1-04)

ON

ON

OFF

OFF

OFF

Frequency Reference 5 (d1-05)

OFF

OFF

ON

OFF

OFF

Frequency Reference 6 (d1-06)

ON

OFF

ON

OFF

OFF

Frequency Reference 7 (d1-07)

OFF

ON

ON

OFF

OFF

Frequency Reference 8 (d1-08)

ON

ON

ON

OFF

OFF

Frequency Reference 9 (d1-09)

OFF

OFF

OFF

ON

OFF

Frequency Reference 10 (d1-10)

ON

OFF

OFF

ON

OFF

Frequency Reference 11 (d1-11)

OFF

ON

OFF

ON

OFF

Frequency Reference 12 (d1-12)

ON

ON

OFF

ON

OFF

Frequency Reference 13 (d1-13)

OFF

OFF

ON

ON

OFF

Frequency Reference 14 (d1-14)

ON

OFF

ON

ON

OFF

Frequency Reference 15 (d1-15)

OFF

ON

ON

ON

OFF

Frequency Reference 16 (d1-16)

ON

ON

ON

ON

OFF

Jog Frequency Reference (d1-17)

<1>

ON

<1> The Jog frequency overrides all other frequency references.

4.6 Basic Drive Setup Adjustments