Auto-tuning operation example, Selecting the type of auto-tuning, Enter data from the motor nameplate – Yaskawa CIMR-AU 200V Drives User Manual

Page 191: 7 auto-tuning, Press or until the auto-tuning display appears, Press to begin setting parameters, Press to display the value for t1-01, Save the setting by pressing, Press to view the default setting, Press

Advertising
background image

u

Auto-Tuning Operation Example

The following example demonstrates Rotational Auto-Tuning when using OLV (A1-02 = 2) and CLV (A1-02 = 3).

n

Selecting the Type of Auto-Tuning

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

2. Press

or

until the Auto-Tuning display appears.

HELP

- MODE -

PRG

Auto-Tuning

DATA

AUTO

FWD

3. Press

to begin setting parameters.

- A.TUNE -

T1-

01

= 0

*0*

Standard Tuning

PRG

Tuning Mode Sel

Rdy

ESC

FWD

DATA

4. Press

to display the value for T1-01.

<1>

- A.TUNE -

T1-01=

0

*0*

Standard Tuning

PRG

Tuning Mode Sel

Rdy

FWD

“0”

5. Save the setting by pressing

.

Entry Accepted

6. The display automatically returns to the display shown in Step 3.

- A.TUNE -

T1-

01

= 0

*0*

Standard Tuning

PRG

Tuning Mode Sel

Rdy

ESC

FWD

DATA

<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1-oo = 16).

n

Enter Data from the Motor Nameplate

After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.

Note:

These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.

Step

Display/Result

1. Press

to access the motor output power parameter T1-02.

- A.TUNE -

T1-

02

= 0.75kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

ESC

FWD

DATA

“0.75kW”

2. Press

to view the default setting.

- A.TUNE -

T1-02=

0

00.75kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

FWD

“0.75kW”

3. Press

F1

left

,

F2

right

,

,

, and

to enter the motor power nameplate data in

kW.

- A.TUNE -

T1-02= 000.4

0

kW

(0.00 ~ 650.00)

PRG

Mtr Rated Power

Rdy

FWD

“0.75kW”

4. Press

to save the setting.

Entry Accepted

4.7 Auto-Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

191

4

Start-Up Programming & Operation

Advertising