Yaskawa CIMR-AU 200V Drives User Manual

Page 204

Advertising
background image

EF4

External Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External Fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

External Fault (input terminal S8)
External fault at multi-function input terminal S8.

Cause

Possible Solution

An external device tripped an alarm function Remove the cause of the external fault and reset the fault.

Wiring is incorrect

• Properly connect the signal lines to the terminals assigned for external fault detection

(H1-oo = 20 to 2B).

• Reconnect the signal line.

Multi-function contact input setting is

incorrect

• Check for unused terminals set for H1-oo = 20 to 2B (External Fault).
• Change the terminal settings.

Digital Operator Display

Fault Name

Err

EEPROM Write Error

Data cannot be written to the EEPROM

FAn

Internal Fan Fault
Fan or magnetic contactor failure

FbH

Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12

to 2 or 5 to enable fault detection.

FbL

PID Feedback Loss
PID feedback loss detection is programmed to trigger a fault (b5-12 = 2 or 5) and the PID feedback level

is below the detection level set to b5-13 for longer than the time set to b5-14.

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

Cause

Possible Solution

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

A damaged motor cable is creating a short

circuit

• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.

Excessive leakage current at the drive output

• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.

The drive performed a current offset

adjustment while the motor was rotating

• The set value exceeds the allowable setting range while the drive automatically adjusts the current

offset. This generally only happens when attempting to restart a PM motor that is coasting to stop.

• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.

Note:

Speed Searches 1 and 2 are the same when using OLV/PM.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

5.2 Fault Detection

204

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide