Figure 7.11 – Yaskawa CIMR-AU 200V Drives User Manual

Page 242

Advertising
background image

Table 7.6 PG Encoder Cable Types

Length

Type

Length

Type

10 m (32 ft.)

W5010

50 m (164 ft.)

W5050

30 m (98 ft.)

W5030

100 m (328 ft.)

W5100

PG-X3 Parameter Settings

• Connecting a Single-Pulse Encoder in V/f with PG Control Mode: Connect the pulse output from the PG to the option and

set F1-21 to 0.

• Connecting a Two-Pulse Encoder: Connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.

When using a two-pulse encoder in CLV control mode, connect pulse outputs A and B from the encoder to the corresponding

terminals on the option.

• Connecting a Two-Pulse Encoder with Z Marker Pulse: Connect the A, B, and Z pulse outputs to the corresponding terminals

on the option.

Control Method

V/f with PG

Closed Loop Vector

No. of Encoders

1 (CN5-C)

2 (CN5-B)

1 (CN5-C)

2 (CN5-B)

Single Pulse (A)

F1-21 = 0

F1-37 = 0

N/A

N/A

Two Pulse (AB Quadrature)

F1-21 = 1

F1-37 = 1

No setting required

No setting required

Two Pulse with Marker (ABZ)

F1-21 = 1

F1-37 = 1

No setting required

No setting required

PG-X3 Connection Diagram

Refer to PG-X3 Option Terminal Functions on page 243

for a detailed description of the option board terminal functions.

U/T1
V/T1

W/T1

R/L1
S/L2
T/L3

A+
A-

B-

Z-

B+

Z+

a+
a-

b-

z-

b+

z+

FE

IP
IG

IP12

IP5

IG

TB1

SG

SD

TB2

PG

NC

CN5-B

or

CN5-C

A

pulse

monitor signal

Ground wire

B

pulse

monitor signal

Z pulse monitor signal

YASKAWA

Drive

PG- X3

Option

CN3

Motor

FE

twisted-pair shielded line

main circuit terminal

control circuit terminal

<1>

Figure 7.11 PG-X3 Option and Encoder Connection Diagram

<1> Ground the shield on the PG side and the drive side. If electrical signal interference problems arise in the PG signal,

remove the shield ground from one end of the signal line or remove the shield ground connection on both ends.

Note:

The PG-X3 option reads a maximum input frequency of 300 kHz from the PG encoder. Select a PG encoder with an output pulse frequency

of maximum 300 kHz when operating at maximum speed.

Take the following steps to prevent erroneous operation caused by noise interference:

7.1 Option Card Installation

242

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide