E5: pm motor settings – Yaskawa CIMR-AU 200V Drives User Manual

Page 291

Advertising
background image

u

E5: PM Motor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E5-01

(0329)

<1>

Motor Code Selection

(for PM Motors)

PM Mtr Code Sel

Enter the Yaskawa motor code for the PM motor being used.

Various motor parameters are automatically set based on the

value of this parameter. Settings that were changed manually

will be overwritten by the defaults of the selected motor code.

Note:

1. Set to FFFF when using a non-Yaskawa PM

motor or a special motor.

2. If an alarm or hunting occurs despite using a

motor code, enter the value indicated on the

nameplate.

Refer to Auto-Tuning for

Permanent Magnet Motors on page 188

for

details.

Default:

<2>

Min.: 0000
Max.: FFFF

<3>

E5-02

(032A)

<1>

Motor Rated Power (for

PM Motors)

PM Mtr Capacity

Sets the rated capacity of the motor.

Default:

<4>

Min.: 0.10 kW

Max.: 650.00 kW

E5-03

(032B)

<1>

Motor Rated Current (for

PM Motors)

PM Mtr Rated FLA

Sets the motor rated current.

Default:

<4>

Min: 10% of

drive rated

current

Max: 200% of

drive rated
current

<5>

E5-04

(032C)

<1>

Number of Motor Poles

(for PM Motors)

PM Motor Poles

Sets the number of motor poles.

Default:

<4>

Min.: 2

Max.: 48

E5-05

(032D)

<1>

Motor Stator Resistance

(for PM Motors)

PM Mtr Arm Ohms

Set the resistance for each motor phase.

Default:

<4>

Min.: 0.000 Ω

Max.: 65.000 Ω

E5-06

(032E)

<1>

Motor d-Axis

Inductance (for PM

Motors)

PM Mtr d Induct

Sets the d-Axis inductance for the PM motor.

Default:

<4>

Min.: 0.00 mH

Max.: 300.00 mH

E5-07

(032F)

<1>

Motor q-Axis

Inductance (for PM

Motors)

PM Mtr q Induct

Sets the q-Axis inductance for the PM motor.

Default:

<4>

Min.: 0.00 mH

Max.: 600.00 mH

E5-09

(0331)

<1>

Motor Induction Voltage

Constant 1 (for PM

Motors)

PM Mtr Ind V 1

Sets the induced phase peak voltage in units of 0.1 mV/(rad/s)

[electrical angle]. Set this parameter when using a Yaskawa

SSR1-Series PM motor with derated torque, or a Yaskawa

SST4-Series motor with constant torque.

Set E5-24 to 0 when setting this parameter.

Default:

<4>

Min.: 0.0 mV/

(rad/s)

Max.: 2000.0

mV/

(rad/s)

E5-11

(0333)

Encoder Z Pulse Offset

(for PM Motors)

Enc Z-Pulse Offs

Sets the offset between the rotor magnetic axis and the Z Pulse

of an incremental encoder during Z Pulse offset tuning.

Default: 0.0 deg

Min.: -180

Max.: 180

E5-24

(0353)

<1>

Motor Induction Voltage

Constant 2 (for PM

Motors)

PM Mtr Ind V 2

Sets the induced phase-to-phase rms voltage in units of 0.1 mV/

(r/min) [mechanical angle]. Set this parameter when using a

Yaskawa SMRA-Series SPM motor.

Default:

<4>

Min.: 0.0 mV/

(r/min)

Max.: 6500.0

mV/

(r/min)

E5-25

(035E)

Polarity Switch for

Initial Polarity

Estimation Timeout (for

PM Motors)

RotPolarityInvrs

0: Disabled

1: Enabled

Switches polarity for initial polarity estimation.

0: Disabled

1: Enabled

There is normally no need to change this parameter from the

default value.

If “Sd = 1” is listed on the nameplate or in a test report for a

Yaskawa motor, this parameter should be set to 1.

Note:

Available control mode varies by drive model:

2A0004 to 2A0415 and 4A0002 to 4A0675:

Available when A1-02 = 6, 7

4A0930 and 4A1200:

Available when A1-02 = 5, 6, or 7.

Default: 0

Range: 0, 1

<1> Setting value is not reset to the default when drive is initialized.
<2> Default setting is determined by parameters A1-02, Control Method Selection, o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.

B.5 E: Motor Parameters

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

291

B

Parameter List