Csa standards compliance, Drive motor overload protection – Yaskawa CIMR-AU 200V Drives User Manual

Page 364

Advertising
background image

<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> Class L fuse is also approved for this rating.

Wiring Fuses for Models 4A0930 and 4A1200

NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices

to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage

current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from

Table 3.2

.

Table C.9 Input Fuses for Models 4A0930 and 4A1200

Voltage

Class

Model

Selection

Input Fuse (Example)

Input Voltage

Current

Pre-arc

I

2

t (A

2

s)

Model

Manufacturer

Rating

Pre-arc

I

2

t (A

2

s)

Three-

Phase

400 V

Class

4A0930

480 V

1500 A

140000 to

3100000

CS5F-1200

Fuji Electric

AC500 V, 1200 A

276000

FWH-1200A

Bussman

AC500 V, 1200 A

4A1200

480 V

1500 A

320000 to

3100000

CS5F-1500

Fuji Electric

AC500 V, 1500 A

351000

FWH-1600A

Bussman

AC500 V, 1600 A

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL listed Class 2 power supply source or equivalent only.

Table C.10 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Open Collector Outputs

P1, P2, PC, DM+, DM-

Requires class 2 power supply

Digital inputs

S1 to S8, SC, HC, H1, H2

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

Analog inputs / outputs

+V, -V, A1, A2, A3, AC, AM, FM

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

n

Drive Short Circuit Rating

The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac

maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by Bussmann

Type FWH or FWP fuses as specified in

Factory Recommended Branch Circuit Protection

on page

346

.

u

CSA Standards Compliance

Figure C.8 CSA Mark

n

CSA for Industrial Control Equipment

The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor

overload protection is UL listed and in accordance with the NEC and CEC.

C.2 UL and CSA Standards

364