B3-01: speed search selection at start – Yaskawa CIMR-AU 200V Drives User Manual

Page 165

Advertising
background image

Output

Frequency

Time

b2-13

Short Circuit

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 4.19 Short-Circuit Braking at Stop in OLV/PM and AOLV/PM

Note:

If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the

E1-09 value. The drive will not perform short-circuit braking when b2-01 = E1-09 = 0 Hz.

CLV and CLV/PM (A1-02 = 3, 7)

For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at Stop. When

the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04.

Time

Zero Speed

Control

b2-04

E1-09 Min. Frequency
b2-01 Zero Speed Level

Output

Frequency

Figure 4.20 Zero Speed Control at Stop in CLV and CLV/PM

Note:

If b2-01 is set to lower than E1-09 (Minimum Frequency), then Zero Speed Control begins at the frequency set to E1-09.

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

Determined by

A1-02

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search

is complete.

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

165

4

Start-Up Programming & Operation