O3: copy function, O4: maintenance monitor settings – Yaskawa CIMR-AU 200V Drives User Manual

Page 328

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o2-04

(0508) Drive Model Selection Inverter Model #

Enter the drive model. Setting required only if installing a new

control board.

Default:

Determined by

drive capacity

o2-05

(0509)

Frequency Reference

Setting Method

Selection

Oper Ref Method

0: Disabled

1: Enabled

0: ENTER key must be pressed to enter a frequency reference.

1: ENTER key is not required. The frequency reference can be

adjusted using the up and down arrow keys only.

Default: 0

Range: 0, 1

o2-06

(050A)

Operation Selection

when Digital Operator is

Disconnected

Oper Discon Det

0: Disabled

1: Enabled

0: The drive continues operating if the digital operator is

disconnected.

1: An oPr fault is triggered and the motor coasts to stop.

Default: 1

Range: 0, 1

o2-07

(0527)

Motor Direction at

Power Up when Using

Operator

For/RevSel@PwrUp

0: Forward

1: Reverse

0: Forward

1: Reverse

This parameter requires assigning drive operation to the digital

operator.

Default: 0

Range: 0, 1

o2-09

(050D)

Factory use.

o2-19

(050D)

<1>

Selection of Parameter

Write during Uv

ParameterSet Sel

0: Disabled

1: Enabled

Selects whether parameter settings can be changed during a DC

bus undervoltage condition. To be used with 24 V Power Supply

option (PS-A10L, PS-A10H) revision B or later.

0: Disabled

1: Enabled

Note:

1. This parameter is not available in models

4A0930 and 4A1200.

2. Enabling this function may trigger a CPF06

fault when used with a 24 V Power Supply

option revision earlier than B, as the parameter

changes might not occur correctly.

Default: 0

Range: 0, 1

<1> Available in drive software versions PRG: 1019 and later.

u

o3: Copy Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o3-01

(0515) Copy Function Selection

COPY SELECT

0: COPY SELECT

1: INV→OP READ

2: OP→INV WRITE

3: OP←→INV

VERIFY

0: Copy select

1: INV → OP READ (Read parameters from the drive, saving

them onto the digital operator).

2: OP → INV WRITE (Copy parameters from the digital

operator, writing them to the drive).

3: OP → INV VERIFY (Verify that parameter settings match the

data saved on the operator).

To read the drive parameter settings into the digital operator, set

o3-02 to 1 (to allow reading).

Default: 0

Range: 0 to 3

o3-02

(0516) Copy Allowed Selection

Read Allowable

0: Disabled

1: Enabled

Selects whether the read operation (o3-01 = 1) is enabled or

disabled.

0: Read operation prohibited

1: Read operation allowed

Default: 0

Range: 0, 1

u

o4: Maintenance Monitor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o4-01

(050B)

Cumulative Operation

Time Setting

DrvElapsTimeCnt

Sets the value for the cumulative operation time of the drive in

units of 10 h.

Default: 0

Min.: 0

Max.: 9999

o4-02

(050C)

Cumulative Operation

Time Selection

ElapsTimeCntSet

0: Power-On Time

1: Running Time

0: Logs power-on time

1: Logs operation time when the drive output is active (output

operation time).

Default: 0

Range: 0, 1

o4-03

(050E)

Cooling Fan Operation

Time Setting

FanElapsTimeCn

Sets the value of the fan operation time monitor U4-03 in units

of 10 h.

Default: 0

Min.: 0

Max.: 9999

B.10 o: Operator-Related Settings

328

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide