A.2 power ratings – Yaskawa CIMR-AU 200V Drives User Manual

Page 249

Advertising
background image

A.2 Power Ratings

u

Three-Phase 200 V Class Drive Models 2A0004 to 2A0030

Table A.2 Power Ratings (Three-Phase 200 V Class)

Item

Specification

Drive Model

2A0004 2A0006 2A0008 2A0010 2A0012 2A0018 2A0021 2A0030

Maximum Applicable Motor

Capacity (HP)

<1>

ND Rating

0.75

1

2

3

3

5

7.5

10

HD Rating

0.75

1

2

2

3

3

5

7.5

Input

Input Current (A)

<2>

ND Rating

3.9

7.3

8.8

10.8

13.9

18.5

24

37

HD Rating

2.9

5.8

7

7.5

11

15.6

18.9

28

Rated Voltage

Rated Frequency

Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc

<3>

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

1.8

3.3

4.0

4.9

6.4

8.5

11

17

HD Rating

1.3

2.7

3.2

3.4

5.0

7.1

8.6

13

Output

Rated Output Capacity

(kVA)

<4>

ND Rating

<5>

1.3

2.3

3

3.7

4.6

6.7

8

11.4

HD Rating

<6>

1.2

1.9

2.6

3

4.2

5.3

6.7

9.5

Rated Output Current (A)

ND Rating

<5>

3.5

6

8

9.6

12

17.5

21

30

HD Rating

<6>

3.2

5

6.9

8

11

14

17.5

25

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User adjustable between 1 and 15 kHz

Maximum Output Voltage (V)

Three-phase 200 to 240 V (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating..

A.2 Power Ratings

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide