B.5 e: motor parameters – Yaskawa CIMR-AU 200V Drives User Manual

Page 287

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E1-04

(0303)

Maximum Output

Frequency

Max Frequency

Parameters E1-04 and E1-06 to E1-13 can only be changed

when E1-03 is set to F.

To set linear V/f characteristics, set the same values for E1-07

and E1-09.

In this case, the setting for E1-08 will be disregarded. Ensure

that the five frequencies are set according to the following rules

to prevent triggering an oPE10 fault:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Setting E1-11 to 0 disables both E1-11 and E1-12 and the above

conditions do not apply.

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

Note:

Some parameters may not be available

depending on the control mode.

• E1-07, E1-08, and E1-10 are available only in the following

control modes: V/f Control, V/f with PG, Open Loop Vector.

• E1-11, E1-12, and E1-13 are available only in the following

control modes: V/f Control, V/f with PG, Open Loop Vector,

Closed Loop Vector.

Default:

<4> <5>

Min.: 40.0
Max.: 400.0

<6>

174

E1-05

(0304)

Maximum Voltage

Max Voltage

Default:

<4> <5>

Min.: 0.0 V
Max.: 255.0 V

<1>

174

E1-06

(0305)

Base Frequency

Base Frequency

Default:

<4> <5>

Min.: 0.0
Max.: E1-04

<6>

174

E1-07

(0306)

Middle Output

Frequency

Mid Frequency A

Default:

<4>

Min.: 0.0

Max.: E1-04

174

E1-08

(0307)

Middle Output

Frequency Voltage

Mid Voltage A

Default:

<4>

Min.: 0.0 V
Max.: 255.0 V

<1>

174

E1-09

(0308)

Minimum Output

Frequency

Min Frequency

Default:

<4> <5>

Min.: 0.0
Max.: E1-04

<6>

174

E1-10

(0309)

Minimum Output

Frequency Voltage

Min Voltage

Default:

<4>

Min.: 0.0 V
Max.: 255.0 V

<1>

174

E1-11

(030A)

<8>

Middle Output

Frequency 2

Mid Frequency B

Default: 0.0 Hz

Min.: 0.0

Max.: E1-04

174

E1-12

(030B)

<8>

Middle Output

Frequency Voltage 2

Mid Voltage B

Default: 0.0 V

Min.: 0.0
Max.: 255.0 V

<1>

174

E1-13

(030C) Base Voltage

Base Voltage

Default: 0.0 V

<7>

Min.: 0.0
Max.: 255.0 V

<1>

174

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> The setting value is F in OLV modes.
<4> Default setting is determined by parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<5> Default setting is determined by parameter E5-01, Motor Code Selection.
<6> In OLV/PM, setting range varies according to the motor code entered to E5-01. The setting range is 0.0 to 400.0 Hz when E5-01 is set to FFFF.
<7> When E1-13, Base Voltage, is set to 0.0, output voltage is controlled with E1-05, Maximum Voltage, = E1-13. When Auto-Tuning is performed,

E1-05 and E1-13 are automatically set to the same value.

<8> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.

B.5 E: Motor Parameters

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

287