u

E2: Motor 1 Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E2-01

(030E) Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps.

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated
current

<2>

175

E2-02

(030F) Motor Rated Slip

Motor Rated Slip

Sets the motor rated slip. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 Hz

Max.: 20.00 Hz

E2-03

(0310)

Motor No-Load Current No-Load Current

Sets the no-load current for the motor. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0 A
Max.: E2-01

<2>

E2-04

(0311)

Number of Motor Poles Number of Poles

Sets the number of motor poles. Automatically set during

Auto-Tuning.

Default: 4

Min.: 2

Max.: 48

E2-05

(0312)

Motor Line-to-Line

Resistance

Term Resistance

Sets the phase-to-phase motor resistance. Automatically set

during Auto-Tuning.

Note:

The units are expressed in mΩ in models 4A0930

and 4A1200.

Default:

<1>

Min.: 0.000 Ω

Max.: 65.000 Ω

E2-06

(0313)

Motor Leakage

Inductance

Leak Inductance

Sets the voltage drop due to motor leakage inductance as a

percentage of motor rated voltage. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.0%

Max.: 40.0%

E2-07

(0314)

Motor Iron-Core

Saturation Coefficient 1 Saturation Comp1

Sets the motor iron saturation coefficient at 50% of magnetic

flux. Automatically set during Auto-Tuning.

Default: 0.50

Min.: 0.00

Max.: 0.50

E2-08

(0315)

Motor Iron-Core

Saturation Coefficient 2 Saturation Comp2

Sets the motor iron saturation coefficient at 75% of magnetic

flux. Automatically set during Auto-Tuning.

Default: 0.75

Min.: E2-07

Max.: 0.75

E2-09

(0316)

Motor Mechanical Loss Mechanical Loss

Sets the motor mechanical loss as a percentage of motor rated

power (kW).

Default: 0.0%

Min.: 0.0

Max.: 10.0

E2-10

(0317)

Motor Iron Loss for

Torque Compensation

Motor Iron Loss

Sets the motor iron loss.

Default:

<1>

Min.: 0 W

Max.: 65535 W

E2-11

(0318)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power in kilowatts (1 HP = 0.746 kW).

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00 kW

<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

B.5 E: Motor Parameters

288