Drive Model

Fuse Type

Manufacturer: Bussmann

Model

Fuse Ampere Rating (A)

5A0062

<1>

FWP-250A

250

5A0077

<1>

FWP-250A

250

5A0099

<1>

FWP-250A

250

5A0125

<1>

FWP-350A

350

5A0145

<1>

FWP-350A

350

5A0192

<1>

FWP-600A

600

5A0242

<1>

FWP-600A

600

<1> 600 V class drives are not compliant with European Standards.

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

n

CE Standards Compliance for DC Power Supply Input

Install the fuses in the following tables to meet CE standards.

M

M

W/T3

Drive

V/T2

U/T1

+1

_

W/T3

Drive

V/T2

U/T1

+1

_

+

_

Fuse

Fuse

DC power supply

(converter)

Figure C.2 Example of DC Power Supply Input (Two A1000 Drives Connected in Series)

Note:

1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.

Refer to Standard Connection Diagram on page 106

for an AC power supply.

3. The recommended fuses and fuse holders are made by Fuji Electric.

C.1 European Standards