E4: motor 2 parameters – Yaskawa CIMR-AU 200V Drives User Manual

Page 290

Advertising
background image

u

E4: Motor 2 Parameters

These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E4-01

(0321)

Motor 2 Rated Current

Motor Rated FLA

Sets the full load current for motor 2. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated
current

<2>

E4-02

(0322)

Motor 2 Rated Slip

Motor Rated Slip

Sets the rated slip for motor 2. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 Hz

Max.: 20.00 Hz

E4-03

(0323)

Motor 2 Rated No-Load

Current

No-Load Current

Sets the no-load current for motor 2. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0 A
Max.: E4-01

<2>

E4-04

(0324)

Motor 2 Motor Poles

Number of Poles

Sets the number of poles of motor 2. Automatically set during

Auto-Tuning.

Default: 4

Min.: 2

Max.: 48

E4-05

(0325)

Motor 2 Line-to-Line

Resistance

Term Resistance

Sets the phase-to-phase resistance for motor 2. Automatically

set during Auto-Tuning.

Note:

The units are expressed in mΩ in models 4A0930

and 4A1200.

Default:

<1>

Min.: 0.000 Ω

Max.: 65.000 Ω

E4-06

(0326)

Motor 2 Leakage

Inductance

Leak Inductance

Sets the voltage drop for motor 2 due to motor leakage

inductance as a percentage of rated voltage. Automatically set

during Auto-Tuning.

Default:

<1>

Min: 0.0%

Max: 40.0%

E4-07

(0343)

Motor 2 Motor Iron-

Core Saturation

Coefficient 1

Saturation Comp1

Set to the motor iron saturation coefficient at 50% of magnetic

flux for motor 2. Automatically set during Auto-Tuning.

Default: 0.50

Min.: 0.00

Max.: 0.50

E4-08

(0344)

Motor 2 Motor Iron-

Core Saturation

Coefficient 2

Saturation Comp2

Set to the motor iron saturation coefficient at 75% of magnetic

flux for motor 2. This value is automatically set during

Auto-Tuning.

Default: 0.75

Min.: E4-07

Max.: 0.75

E4-09

(033F)

Motor 2 Mechanical

Loss

Mechanical Loss

Sets the motor mechanical loss for motor 2 as a percentage of

motor rated power (kW).

There is normally no need to change this parameter from the

default value.

Default: 0.0%

Min.: 0.0

Max.: 10.0

E4-10

(0340)

Motor 2 Iron Loss

Motor Iron Loss

Sets the motor iron loss.

Default:

<1>

Min.: 0 W

Max.: 65535 W

E4-11

(0327)

Motor 2 Rated Power

Mtr Rated Power

Sets the motor rated capacity in kW. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00 kW

<1> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

B.5 E: Motor Parameters

290