H3-05: terminal a3 signal level selection, Selects the input signal level for analog input a3 – Yaskawa CIMR-AU 200V Drives User Manual

Page 179

Advertising
background image

n

H3-03, H3-04: Terminal A1 Gain and Bias Settings

Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.

No.

Name

Setting Range

Default

H3-03

Terminal A1 Gain Setting

-999.9 to 999.9%

100.0%

H3-04

Terminal A1 Bias Setting

-999.9 to 999.9%

0.0%

Setting Examples

• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since

the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04

above 5 Vdc.

100%

-100%

5 V

10 V

-5 V

-10 V

E1-04

E1-04

H3-01 = 0

H3-01 = 1

0 V

10 V

5 V

0 V

Gain = 200 %

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Gain = -200 %

Figure 4.29 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.

2.0 V

10 V

-6.0 V

-10 V

E1-04

0

-100%

-150%

2.0 V

10 V

100 %

Frequency
reference

-25%

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

H3-01 = 1

100%

Analog Input

Voltage

Analog Input

Voltage

Figure 4.30 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-05: Terminal A3 Signal Level Selection

Selects the input signal level for analog input A3.

No.

Name

Setting Range

Default

H3-05

Terminal A3 Signal Level Selection

0, 1

0

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. See the explanation provided for H3-01.

Refer to Setting 0: 0 to 10 Vdc on page 178

.

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

179

4

Start-Up Programming & Operation