CONTROL CIRCUIT
TERMINALS

MAIN CIRCUIT
TERMINALS

(2) GROUND
TERMINALS

Unit: in. [mm]

Figure 2.42 Models 4T0139 and 4T0165

Table 2.23 12-Pulse Models 4T0139 and 4T0165 Terminal and Wire Specifications for Main Circuit and Ground

Drive Model

Terminal

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4T0139

<1>

4T0165

<1>

R/L1, S/L2, T/L3

22 to 1/0 (0.3 to 53.5)

M6

2.5 to 3.0

(22 to 1/0)

R1/L11, S1/L21, T1/L31
⊖, ⊕3
U/T1, V/T2, W/T3

6 to 250 (13.3 to 127)

M8

15.0 (132.8)

Refer to applicable codes for wire size

M10

18 to 23

(159.3 to 203.6)

<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.

2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide