2 short commissioning (factory setting), 1 switch-on sequence, Short commissioning (factory setting) – Lenze 8200 Frequency inverters User Manual

Page 107: Switch-on sequence, Commissioning

Advertising
background image

Commissioning

8200SHB0199

5-2

5.2

Short commissioning (factory setting)

5.2.1

Switch-on sequence

Step

1.Connect to the mains.

The controller is ready for operation after approx. 2 seconds.

2.Enter the direction of rotation.

-

CW rotation:
- Apply a LOW signal to terminal E4 (0 ... + 3 V).

-

CCW rotation:
- Apply a HIGH signal to terminal E4 (+ 12 ... + 30 V).

3.Enter the setpoint.

Apply a voltage 0 ... + 10 V to terminal 8.

4.Enable controller.

Apply a HIGH signal (+ 12 ... + 30 V) to terminal 28.

5.The drive is now running with factory setting.

5.2.2

Factory setting of the most important drive parameters

Setting

Code

Factory setting

Adaptation to the
application

Operating mode

C001

-0-

Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB

See code table, chapter 7.8
for “Standard”

See code table, chapter 7.9
for “HVAC”

Terminal configuration

C007

-0-

E4

E3

E2

E1

CW/CCW DC injection brake JOG1/2/3

See code table, chapter 7.8
for “Standard”

See code table, chapter 7.9
for “HVAC”

Machine data

Chapter 5.3 ff.

Speed range

Min. field frequency

C010

0.00 Hz

Chapter 5.3.1

Speed range

Max. field frequency

C011 50.00 Hz

Chapter 5.3.1

Acceleration
and
deceleration

Acceleration time

C012

5.00 s

Chapter 5.3.2

and
deceleration
times

Deceleration time

C013

5.00 s

Current limit
values

Motor mode

C022

150 %

Chapter 5.3.3

Current limit
values

Generator mode

C023

80 %

Chapter 5.3.3

Drive performance

Chapter 5.4 ff.

Current /
torque/power/

Operating mode

C014

Motor-current control, see
chapter 5.4.2.1

Current /
torque/power/
performance

820X

-0-

Linear characteristic V

f

d

with auto

boost

Motor-current control, see
chapter 5.4.2.1
V/f-characteristic control

with auto boost, chapter

performance

821X/822X/

824X

-4-

Motor-current control

-

with auto boost, chapter
5.4.2.2
with V

min

boost, chapter

V/f-rated frequency

C015

50.0 Hz

-

with V

min

boost, chapter

5.4.2.3

V

min

-setting

C016

5.4.2.3

820X

C016

type-

dependent

821X/822X/

824X

0 %

Slip compensation

C021

0 %

Show/Hide Bookmarks