Network of several drives

8200SHB0199

10-16

10.5

Decentral supply

The DC-bus is supplied via several controllers or supply units connected in parallel
to the mains.

10.5.1

Decentral supply for 820X

820X

U V W

PE

L1

N -UG +UG

820X

U V W

PE

L1

N -UG +UG

Z3

F1 F1*

F1 F1*

Z1 Z1*

Z1 Z1*

F4 F5

F4 F5

-UG +UG

K10

PE

L1

PE

N/L2

K10*

FIG 10-4

Block diagram: Decentral supply of several 820X controllers connected to a network

F1, F1*

Fuses, see Accessories
F1*only for supply voltage 2AC / PE / 190 - 260 V

–0 %/ 45 - 65 Hz –0 %

K10, K10*

Mains contactor
K10*only for supply voltage 2AC / PE / 190 - 260 V

–0 %/ 45 - 65 Hz –0 %

F4, F5

Fuses, DC level, see Accessories

Z1, Z1*

Mains choke/mains filter, see Accessories
Z1*only for supply voltage 2AC / PE / 190 - 260 V

–0 %/ 45 - 65 Hz –0 %

Z3

Brake chopper/brake module, see Accessories

Stop!

For faultless network operation, the following conditions must be fulfilled in addition
to the conditions described in chapter 10.2:

-

In-phase connection on the mains side

-

With two-phase supply

- Cable and overload protection via second assigned mains fuse F1*

- Ensure current and power symmetry by providing a second mains

choke/mains filter Z1*.