Configuration

8200SHB0199

7-44

7.5.11.4 Setpoint input via function ”Motor potentiometer”

Function

The setpoint input via the function ”Motor potentiometer” is only active, if C007 is set accordingly.
(Series “Standard”: see chapter 7.8, “Code table”; series “HVAC”: see chapter 7.9, ”Code table”).
The field frequency is changed via the set acceleration and deceleration times.

Activation
Series “Standard”:

-

C007 = -10-, -11-, -12-, -13-, -21-:

Function

E1

E2

Setpoint = 0 Hz

LOW

LOW

Reduce setpoint until f

dmin

HIGH

LOW

Increase setpoint until f

dmax

LOW

HIGH

Setpoint remains constant

HIGH

HIGH

Series “HVAC”:

-

C007 = -10-, -11-, -12-, -13-, -21-, -23-, -24-, -25-, -26-, -27-, -44-:

Function

E1

E2

E3

3)

E4

3)

Setpoint = 0 Hz (T

iQSP

, C105)

1)

LOW

LOW

LOW

LOW

Reduce setpoint until f

dmin

(T

if

, C013)

2)

HIGH

LOW

HIGH

LOW

Increase setpoint until f

dmax

(T

ir

, C012)

LOW

HIGH

LOW

HIGH

Setpoint remains constant

HIGH

HIGH

HIGH

HIGH

1)

LOW level at terminals E1 and E2 reduces the setpoint along the QSP ramp (C105) until
f

d

= 0 Hz

2)

Only possible, if the setpoint has exceeded f

dmin

before.

3)

Only, if C007 = -44-

Activation of the function “Motor potentiometer” via normally-closed contacts

Series “Standard”:

C007 = -10- ... -13-, -21-

Series “HVAC”:

C007 = -10- ... -13-, -21- ... -27-

C007 = -44-

E1

E2

E3

E4

20

^

STOP = CCW

E1

E2

E3

E4

20

^

STOP = CCW

Important

The setpoint is saved

-

when switching off the mains,

-

when inhibiting the controller,

-

when having fault messages.

Exception:

-

If the control terminals are set to LOW in the event of mains failure (e.g. external voltage supply),
the setpoint 0 Hz will be stored.

-

Activation of the QSP function (C007 = -13-, -21-) resets the motor potentiometer to 0 Hz.

Special features

The terminal configuration C007 = -13- provides an open-circuit protection for quick stop.