Technical Data

8200SHB0199

3-7

150 % overload

8214

8213

8212

8211

Type

EVF8214-E

EVF8213-E

EVF8212-E

EVF8211-E

Order No.

8214-V020

8213-V020

8212-V020

8211-V020

Type

Variant “HVAC”

EVF8214-E-V020

EVF8213-E-V020

EVF8212-E-V020

EVF8211-E-V020

Order No.

Motor voltage

3)

V

M

[V]

0 - 3 x V

mains

/ 0 Hz

¡ 50 Hz, if required up to 480 Hz

Power loss (operation with I

rx

)

P

loss

[W]

55

75

90

100

Power derating

[%/K]

[%/m]

40

•C < T

V

< 50

•C: 2.5 %/K

1000 m a.m.s.l.

h $ 4000 m a.m.s.l.: 5 %/1000 m

Field
frequency

Resolution

Absolute

0.02 Hz

Field
frequency Digital setpoint selection

Accuracy

á0.05 Hz

Analog setpoint selection

Linearity

á0.5 %(max. selected signal level: 5 V or 10 V)

Analog setpoint selection

Temperature
sensitivity

0

¡ 40 •C: +0.4 %

Offset

á0 %

Weight

m [kg]

2.2

2.2

2.2

2.2

Printed in bold

Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I

rx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

4)

Only with variant “HVAC”

*

Chopper frequency of the inverter

Show/Hide Bookmarks