Configuration – Lenze 8200 Frequency inverters User Manual

Page 144

Advertising
background image

Configuration

8200SHB0199

7-7

Acceptance acknowledged with SH + PRG when the controller is
inhibited.

(Labelled with ”[Cxxx]” in the code table.)

The controller only accepts the changed parameter when the controller is inhibited
and after pressing SH + PRG.

1. In the operating level you inhibit the controller by pressing STP.

2. Change from the operating level to the code level by pressing PRG.

3. Select a code with

or

.

4. Change to parameter set PAR1 by pressing SH.

- If necessary, press SH again to change to parameter set PAR 2.

5. If PAR1 or PAR2 is blinking, change the parameter with

or

.

6. Press SH + PRG.

- STO is displayed for approx. 1 s.

- The program jumps back to the code level.

7. Change to the operating level by pressing PRG.

- The changed parameter is now stored permanently.

8. Enable the controller again using RUN.

- The controller now works with the new parameter.

Note!

Fast loading of the factory setting for 820X:
Press the keys

and

at the same time in the parameter level to load the factory

setting of the selected code.