Application examples

8200SHB0199

15-9

Application FIG 15-4:

The air conditioning system of a department store is to be controlled according to
the number of persons present. The fans must circulate an amount of air that
depends on the number of people (e.g. data provided by a person counter).

Functions used

-

Belt monitoring

-

Mains failure detection
- Controlled deceleration and stopping of the drive after mains failure

-

Flying-restart circuit on coasting motor

-

Suppression of mechanical resonances

-

Smooth start/stop with S ramps

Code settings for unit 1:

Code

Name

Possible settings

Code

Name

Lenze

Choice

Info

C001

C2001

Operating mode

-0-

-0-

Setpoint selection via term. 8 (jumper setting see
chapter 4.2.8.2)
Control via terminals parameter setting with 8201BB

C005

C2005

Configuration

-0-

-0-

Operation with open-loop control via terminal 8

C008

C2008

Function relay K1

-1-

-14-

Apparent motor current (C054) < Current threshold
C156 and acceleration finished (Belt monitoring)

C014

C2014

Control mode

-0-

-3-

Square characteristic V

f

d

2

with constant V

min

boost

C142

C2142

Start condition

-1-

-3-

Automatic start, if term. 28 HIGH, flying-restart circuit
active

C156 Current threshold

0

50 %

C182 t

integration

RFG S-shape

0.00

0.50 s

Smooth start / stop

C625 Skip frequency 1

480.00

30.00 HzRemoval of mechanical resonances

C628 Skipping bandwidth, f

skip

0.00

10.00 %

C988 DC-bus voltage threshold for

DC-bus voltage control

0

81 %

Controlled deceleration after mains failure by
changing the parameter set

Motor deceleration after mains failure
Parameter set changeover via DC-bus voltage control

PAR 1

PAR 2 (Code = C2XXX)

C007 = 2
C105 = 0.5 s

C2007 = 0
C2105 = 5.00 s

Note!

Terminal E3 must always be at L-level (PAR2: normal operation; PAR1: QSP)