Configuration

8200SHB0199

7-35

Normalisation

-

Adaptation of a field related parameter to an application datum to be controlled (e.g. pressure,
temperature, flow rate, humidity, speed) under C500 and C501.

-

The following codes are normalised at the same time:
- C010, C011 C017, C019, C037, C038, C039, C046, C049, C050, C051, C181, C625, C626,

C627

-

After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501 (see formulas in chapter 7.6.3).

-

In factory setting, all field related parameters refer to the frequency. Input and display in Hz. The
values of C037, C038, C039, C046, C051, C181 refer to C011.

Factory setting
A percentage of the input or display values
corresponds to the frequency in Hz.

0 %

100 % Setpoint or act. value

C011
[Hz]

Adjustment

The value set under C071 correspond to the following integral action times T

n

.

Values under C071

Integral action time T

n

10 ... 5000

10 ms ... 5000 ms

5000 ... 6000

5 s ... 10 s

6000 ... 7000

10 s ... 100 s

7000 ... 8000

100 s ... 1000 s

8000 ... 9999

1000 s ... 9999 s

Guide values for pressure
control and flow rate

The values in the following table are for guidance for pressure and flow-rate controls. A fine
adjustment is therefore always necessary.
C070, C071 and C072 must be set so that the target value is

-

reached quickly and

-

with minimum overshooting

when the setpoints and actual values are changed.
The differential component K

D

(C072) is usually not required for pressure and flow-rate controls

(set C072 = 0).

Guide values for pressure control and flow rate

Code

Gases

Liquids

C070 (V

P

)

0.1

0.02 ... 0.1

C071
(T

n

)

5000
(5 s)

200 ... 1000
(0.2 s ... 1 s)