Commissioning – Lenze 8200 Frequency inverters User Manual

Page 130

Advertising
background image

Commissioning

8200SHB0199

5-25

Note!

-

For more detailed information on the process controller, see chapter

7.5.10.

-

Calibration of the setpoints and actual values to the application datum under
C500 and C501.
(See chapter 5.4.2.4).

Notes for the adjustment of the dancer controller:

Set the gain Vp (C070), the integral action time T

N

(C071) and the differential

component (C072) so that the original position can be reached quickly with only
minimum overshooting, if the dancer is adjusted manually (change of the act.
value).

For the adjustment start with code C070, then set C071 and C072. C071 must be
deactivated (via terminal E4) when setting C070. C072 must be deactivated (via
0) for setting C071.

Show/Hide Bookmarks

Advertising