Commissioning

8200SHB0199

5-12

5.4.2.3

Optimise V/f-characteristic control with constant V

min

boost

(C014 = -2-/ -3-)

Required codes

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C015 V/f-rated frequency

Standard controllers

C015

820X

50.00

30.0

{0.05 Hz}

960.00

821X/822X/

824X

50.00

7.50

{0.02 Hz}

960.00

C015 V/f-rated frequency

50.00

7.50

{0.02 Hz}

960.00

Variant “HVAC”

C016 V

min

setting

C016

820X

*

0.0

{0.2 %}

40.0

*depends on the unit

821X/822X/

824X

0.0

0.0

{0.2 %}

40.0

C021 Slip compensation

Standard controllers

C021

820X

0.0

0.0

{0.1 %}

12.0

821X/822X/

824X

0.0

0.0

{0.1 %}

20.0

C021 Slip compensation

0.0

-50.0

{0.1 %}

50.0 * depends on

the unit

Variant “HVAC”

C021 Slip compensation

0.0

-50.0

{0.1 %}

50.0 * depends on

the unit

Variant “HVAC”

C077* Gain I

max

controller

0.25

0.00

{0.01}

1.00

Variant “HVAC”
(see chapter 7.5.4)

C078* Integral action time

I

max

controller

65

12

{1 ms}

9990

Variant “HVAC”
(see chapter 7.5.4)

Setting sequence

1.If necessary, select V/f

characteristic (C014).

2.Select V/f-rated frequency

(C015).

-

The V/f-rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.

-

An internal mains voltage compensation compensates deviations in the mains during operation.
Therefore, they do not have to be considered for the setting of C015.

Adjustment
Calculate the frequency to be set under C015:

C015 [Hz]

400 V

V

rmotor

[V]

ô f

dr

[Hz]

V

rmotor

Rated voltage to motor nameplate [V]

f

dr

Rated frequency to motor nameplate [Hz]

For standard motors with f

dr

= 50 Hz, the following settings result for C015:

Motor voltage

Motor connection

C015

230/400 V

Y

50 Hz

230/400 V

D

87 Hz