2 mains connection, 1 cable protection/ cable cross-section, 2 mains choke/ mains filter – Lenze 8200 Frequency inverters User Manual

Page 246: 3 controller protection, Mains connection, Cable protection/cable cross-section, Mains choke/mains filter, Controller protection, Network of several drives, 2 mains choke/mains filter

Advertising
background image

Network of several drives

8200SHB0199

10-3

10.2.2

Mains connection

10.2.2.1 Cable protection/cable cross-section

-

Mains fuses and cable cross-section of the mains cables must be selected
according to the mains current which results from the input power P

DC100

%

. Observe national standards, temperatures and other conditions.

-

Rule of thumb for the mains current in networks:

,

€hv†

>$@ 

3

98  И

ф 

9

€hv†

-

See page 10-10.

10.2.2.2 Mains choke/mains filter

-

Use the mains chokes/mains filters assigned to the network operation.
Function:

- Mains-current limitation

- Current/power symmetry of the mains input circuits of the controllers in

decentral network operation.

-

Mains choke/mains filter must be selected according to the mains current
and the required radio interference suppression (see page 10-11).

10.2.2.3 Controller protection

Switch-on conditions

-

Ensure simultaneous mains connection of all controller connected
to the network.

Mains-failure detection at the controller when selecting decentral
supply

-

Monitoring of the mains supply of each controller:

- In the event of failure, the controllers still connected to the mains can be

overloaded.

-

Measure:

- Switch-off the whole drive network, if a mains supply fails.

-

Possibilities for detecting/indicating mains failures:

- Application of mains fuses with alarm contact.

- Application of thermal overcurrent releases (bimetall relay), which is

connected after the mains fuses.

- Application of power switches with thermal and magnetic releases as well

as integrated alarm contact to protect the cable.