Application examples – Lenze 8200 Frequency inverters User Manual

Page 282

Advertising
background image

Application examples

8200SHB0199

15-3

Code settings:

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C001 Operating mode

-0-

-3-

Setpoint selection - control,
parameter setting via LECOM

C005 Configuration

-0-

-7-

Controlled operation, with
analog feedback via term. 8

C007 Terminal configuration

-0-

-26-

Motor potentiometer, JOG,
H/Re

C037 JOG value 1

20.00

16.67 HzFixed reduction to 1/3 of the

rated pressure

C051 Actual PID controller value

Only display of actual
pressure

C070 Gain PID controller

1.00

0.02 ... 0.1

C071 Integral action time PID

controller

100

0.2 ... 1 s

Adaptation to process

C072 Differential component PID

controller

0.0

0.0

Inactive

C074 Influence PID controller

0.0

100.0 %

C111

¤ Monitor signal

-0-

-8-

Actual PID controller value

C238 Frequency precontrol

-1-

-0-

No precontrol

C239 Frequency setting range

-0-

-1-

Unipolar

Direction of rotation
cannot be changed via
the process controller

All other parameters are based on the factory setting.

Set the rated motor data under C088 (rated motor current) and C091 (motor cos

Ö) depending on the motor

connected.

In addition to the setpoint input via fieldbus, the pressure setpoint can also be selected via the 8201BB keypad
(installation up to max. 10 m away from the controller) or via an analog input signal (using the 8274 plug-in module).

Note!

-

For more detailed information on the process controller, see chapter

7.5.10.

-

Calibration of the setpoints and actual values to the application datum under
C500 and C501.
(See chapter 7.6.3)