7 power connections, 1 mains connection, Power connections – Lenze 8200 Frequency inverters User Manual

Page 85: Mains connection, Installation

Advertising
background image

Installation

8200SHB0199

4-28

4.2.7

Power connections

4.2.7.1

Mains connection

Types 8221 to 8227

Types 8241 to 8246

PE

+UG

-UG

L1

L2

L3

PE

L1

L2

L3

-UG

+UG

s

Correct screen connection with screened cables:

-

Connect the screen with suitable clamp to the
conducting control cabinet mounting plate.

-

To improve the screen connection: Connect screen
additionally to the stud next to the power connections.

Correct screen connection with screened cables
(required parts in the accessory kit):

-

Screw sreen plate

on fixing bracket

.

-

Fix screen using cable lugs. Do not use as a strain
relief!

-

To improve the screen connection: Connect the screen
additionally to the stud next to the power connections.

FIG 4-16

Proposal for mains connection 822X/824X

-

Connect the mains cables to the screw terminals L1, L2, L3.

-

Connect cables for brake unit (935X), supply module (934X) or further
controllers in the DC-bus connection to the screw terminals +U

G

, -U

G

at the

top of the controller.

-

Max. permissible cable cross-sections and tightening torques:

Terminals

Type

Max. permissible

cable cross-sections

L1, L2, L3, + U

G

, -U

G

PE connection

8201 - 8214

2.5 mm

2

0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)

1.7 Nm (15 lbin)

8215 - 8218

4 mm

2 1)

0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)

1.7 Nm (15 lbin)

8221 - 8223

25 mm

2 2)

4 Nm (35 lbin)

8224 - 8225

95 mm

2 2)

7 Nm (62 lbin)

8226 - 8227

120 mm

2 2)

12 Nm (106.2 lbin)

8241 - 8246

4 mm

2 1)

0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)

3.4 Nm (30 lbin)

1)

With pin-end connector:

6 mm

2

With wire crimp cap:

4 mm

2

2)

With ring cable lug:

The cross-section is only limited by the cable cut-out in the housing.