4 motor-phase failure detection, Motor-phase failure detection, Configuration – Lenze 8200 Frequency inverters User Manual

Page 210: Only series “hvac

Advertising
background image

Configuration

8200SHB0199

7-73

7.7.4

Motor-phase failure detection

Only series “HVAC”

Setting range 821X: not possible

Setting range 822X/824X:

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C597*

¤ Activation of

motor-phase failure
detection

-0-

-0-

Inactive

-1-

TRIP

-2-

Warning

C599 Current limit for

motor-phase failure
detection

5

1

{1 %}

50

Function

If the function is activated under C597, the controller monitors the motor phases for failure. The
current limit value (C599) defines the threshold when a motor phase failure is indicated. The value
set under C599 corresponds to the percentage of the rated controller current [I

r

].

Activation

-

C597 = -0- function not active

-

C597 = -1- fault message TRIP

-

C597 = -2- warning message

Fault indication

-

8201BB operating module:
- TRIP:

LP1

- Warning:

LP1

-

Fieldbus:
- TRIP:

32

- Warning:

182

Important

C597 and C599 are only stored in parameter set 1.