4 motor-phase failure detection, Motor-phase failure detection, Configuration – Lenze 8200 Frequency inverters User Manual
Page 210: Only series “hvac
Configuration
8200SHB0199
7-73
7.7.4
Motor-phase failure detection
Only series “HVAC”
Setting range 821X: not possible
Setting range 822X/824X:
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C597*
¤ Activation of
motor-phase failure
detection
-0-
-0-
Inactive
-1-
TRIP
-2-
Warning
C599 Current limit for
motor-phase failure
detection
5
1
{1 %}
50
Function
If the function is activated under C597, the controller monitors the motor phases for failure. The
current limit value (C599) defines the threshold when a motor phase failure is indicated. The value
set under C599 corresponds to the percentage of the rated controller current [I
r
].
Activation
-
C597 = -0- function not active
-
C597 = -1- fault message TRIP
-
C597 = -2- warning message
Fault indication
-
8201BB operating module:
- TRIP:
LP1
- Warning:
LP1
-
Fieldbus:
- TRIP:
32
- Warning:
182
Important
C597 and C599 are only stored in parameter set 1.