4 reset of fault messages, Reset of fault messages, Troubleshooting and fault elimination – Lenze 8200 Frequency inverters User Manual

Page 239

Advertising
background image

Troubleshooting and fault elimination

8200SHB0199

8-4

8.4

Reset of fault messages

TRIP

After eliminating the fault, the pulse inhibit will only be reset after the
acknowledgement of TRIP.

Note!

If the TRIP source is still active, the TRIP cannot be reset.

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C170

¤ TRIP-reset selection

-0-

TRIP reset by pressing the STP key
or LOW signal at ctrl. enable or
fieldbus

-1-

Auto-TRIP reset or TRIP reset by
pressing the STP key or LOW signal
at ctrl. enable or fieldbus

C171 Deceleration for

Auto-TRIP reset

0.00

0.00

{0.01 s}

60.00

Function

You can select whether the fault is to be reset automatically or manually.
Auto-TRIP reset does not reset all faults automatically.

Activation

C170 = -0-:

-

TRIP reset (fieldbus)

-

STP key

-

LOW signal at terminal 28

C170 = -1-:

-

Auto-TRIP reset resets all faults after the time set under C171.

-

TRIP reset (fieldbus)

-

STP key

-

LOW signal at terminal 28

Important

-

Mains switching always resets TRIP.

-

With more than 8 auto-TRIP resets within 10 minutes (internal counter), the controller sets TRIP
and indicates rST (counter exceeded).
- With TRIP reset by pressing the STP key or LOW signal at ctrl. enable or fieldbus, the controller

resets the internal counter.