15 indirect torque limitation, Indirect torque limitation, Configuration – Lenze 8200 Frequency inverters User Manual

Page 198: Only “hvac” controllers

Advertising
background image

Configuration

8200SHB0199

7-61

7.5.15

Indirect torque limitation

Only “HVAC” controllers

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C005

-3-

Open loop operation via frequency
input E1 with limitation of the
apparent motor current via
terminal 8

C005 = -3-
possible with
C014 = -2-, -4-

Function

With C005 = -3-, the apparent motor current (indirect torque limitation) can be limited with an
external signal via the analog input terminal 8. Enter a motor current limit.

Adjustment

The influence of the torque limitation is adjusted via the analog input terminal 8
(see chapter 7.5.11.1).

-

The effective current limit is indicated in % in C047.

-

C022 has no influence. The external signal via terminal 8 selects the current limit.

-

C023 remains effective.

Example

Constant mass flow control:

8200

air/discharge

heavy

cold

warm

M

f

light

Fan

mass
flow

m = const.