Configuration

8200SHB0199

7-51

C007

E1

E2

E3

E4

only

series “HVAC”

-40-

D/F

TRIP set

QSP

JOG1

only

series “HVAC”

-41-

D/F

TRIP set

DC injection brake

JOG1

-42-

D/F

TRIP set

DC injection brake

QSP

-43-

D/F

TRIP set

QSP

CW/CCW

-44-

D/F

PAR

DOWN

UP

-45-

D/F

PAR

QSP

CW/CCW

-46-

JOG1

QSP

PAR

H/Re

-47-

JOG1

H/Re

CCW/QSP

CW/QSP

-48-

D/F

I-OFF

DC injection brake

INFL_0

-49-

D/F

QSP

JOG1

INFL_0

-50-

D/F

I-OFF

JOG1

INFL_0

-51-

D/F

I-OFF

PAR

DCB

Function

Depending on your application you can select a function group under C007. A binary signal code at
the digital inputs E1 ... E4 activates the functions.

Important

Response time of the inputs E1 ... E4:

820X

16 ... 24 ms

821X/822X/824X

2.5 ... 4 ms

Special features

820X

The digital inputs E1 ... E4 are without function when using the operating mode ”Control via
LECOM” (C001 = -3-).

821X/822X/824X

With the operating mode ”Control via LECOM” (C001= -3-), the functions ”TRIP set” and ”QSP”
remain effective.

Series “HVAC”

With the operating mode ”Control via LECOM” (C001= -3-), the functions ”TRIP set” and ”QSP”
remain effective. They can be switched-off with the priority mask (C115).

-

The levels for the input terminals can be inverter under C114.

-

Use the following terminal configuration, if terminal E1 is used for the setpoint or the act. value:
(see chapter 7.5.14.9)
- C007 = -28- ... -45, -48- ... -51-