10 pid controller as process controller, Pid controller as process controller, Configuration – Lenze 8200 Frequency inverters User Manual

Page 171: Only “hvac” controllers

Advertising
background image

Configuration

8200SHB0199

7-34

7.5.10

PID controller as process controller

Only “HVAC” controllers

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C070 Gain

PID controller

1.00

0.00

{0.01}

300.00

0.0 = P-component
not active

C071 Integral action time

PID controller

100

10

9999 See table under

“Adjustment”

9999 = I-component
not active

C072 Differential

component
PID controller

0.0

0.0

{0.1}

5.0

0.0 = D-component
not active

C074 Influence PID

controller

0.0

0.0

{0.1 %}

100.0

ref. to C011 (f

dmax

)

Function

The process controller is active with the following configuration:

Configuration

Terminal function

C005 = -6-

Setpoint via terminal 8 (JOG value, motor potentiometer, fieldbus)
Actual value via terminal E1

C005 = -7-

Setpoint via terminal E1 (JOG value, motor potentiometer,
fieldbus)
Actual value via terminal 8

Setpoints

Setpoints can be selected and displayed under the following codes:

Code

Setpoint selection and display

C037

JOG value1 [Hz]

C038

JOG value2 [Hz]

C039

JOG value3 [Hz]

C046

Frequency setpoint [Hz]
(Only with keypad 8201BB or interface)

C181

Setpoint PID controller [Hz]

Actual value

The actual value can be displayed under the following codes:

Code

Actual value display

C051

Actual value PID controller [Hz]

A digital frequency can be selected as actual value via terminal E1 (see chapter 4.2.8.3).