4 normalisation of an application datum, Normalisation of an application datum, Commissioning – Lenze 8200 Frequency inverters User Manual

Page 120

Advertising
background image

Commissioning

8200SHB0199

5-15

5.4.2.4

Normalisation of an application datum

820X setting range:

Function not available.

Setting range 821X/822X/824X:

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C500* Display factor

Application datum -
numerator

2000

1

{1}

25000

C501* Display factor

Application datum -
denominator

10

1

{1}

25000

Function

Adaptation of field-frequency related parameters

-

C010, C011, C017, C019, C037, C038, C039, C046, C049, C050 and

-

for controllers of the “HVAC” series C051, C181, C625, C626, C627 additionally

to an application datum to be controlled, e.g. pressure, temperature, flow rate, humidity or speed.
The normalisation

-

implements an absolute or relative selection or display of an application datum,

-

is always carried out simultaneously for all codes indicated.

Adjustment

The display value is calculated from:

CXXX

C011

200 ô

C500
C501

Example

The speed setpoint is to be input and displayed as relative or absolute value.
Values: P

set

= 5 bar, if f

dmax

= 50 Hz (C011)

a) Relative normalisation in %

100.00 (%)

50

200 ô

4000

10

e.g. C500 = 4000, C501 = 10

b) Absolute normalisation in physical units

5.00 (bar)

50

200 ô

200

10

e.g. C500 = 200; C501 = 10

Important

-

All codes indicated above are normalised at the same time.

-

After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501.