8200SHB0199

7-46

7.5.11.5 Setpoint input via function ”Motor potentiometer in

combination with JOG value”

Function

The setpoint input via the function ”Motor potentiometer in combination with JOG value” is only
active, if C007 is set accordingly (see chapter 7.8, ”Code table”).
The field frequency is changed:

-

For acceleration over acceleration ramp C012.

-

For deceleration:
- via the deceleration ramp C013 (820X controllers),
- via the quick-stop ramp C105 (821X/822X/824X controllers).

Activation

C007 = -22-:

Function

Setpoint

K1

K2

K3

K4

DOWN

0 Hz

*

*

1

0

CW rotation

determined by E1/E2

*

*

0

0

CCW rotation

determined by E1/E2

*

*

1

1

UP

f

dmax

(C011)

0

1

0

0

CONSTANT

constant

0

0

0

0

JOG

JOG value 1 (C037)

1

*

0

0

*arbitrary

Important

-

In the event of maloperation, i.e. UP = E2 and DOWN = E3 both activated, the controller is set to
0 Hz.

-

The field-frequency value activated via the motor-potentiometer function represents the max. limit
value for the JOG function E1, i.e. it is not possible to activate a JOG value higher than the last
motor-potentiometer value. Smaller values are however possible.

-

In the event of mains disconnection (interruption > approx. 10 s) the last motor potentiometer
value will not be stored, i.e. the new start value is 0 Hz.

-

With CCW rotation (E3 = 1, E4 = 1) the ”DOWN” function changes from E3 = 1 to E4 = 0.

Special features

The function can be influenced through level inversion of the terminals (C114).
(Only series “HVAC”)

E2

E1

20

E3

E4

JOG1

ccw rotation

UP

DOWN

K1

K2

K3

K4

FIG 7-4

Control of the motor-potentiometer function, C007= -22-