Configuration
8200SHB0199
7-32
7.5.9.4
Ramp function generator S-shape
Only “HVAC” controllers
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C182* Integration time
ramp function
generator S-shape
0.00
0.00
{0.01 s}
50.00
Function
An adjustable transmission element (PT1) is connected behind the ramp function generator. The
integration time (T
i
) is set. It rounds the frequency setpoint.
This function enables absolutely smooth starting of the drive.
Adjustment
-
C182 = 0.00
- The ramp function generator work linearly.
-
C182 > 0.00
- The ramp function generator works as S-shape with the time T
i
= C182.
Important
C182 is only stored in parameter set 1.