1 level inversion for digital inputs, Level inversion for digital inputs, Configuration – Lenze 8200 Frequency inverters User Manual
Page 189: Only “hvac” controllers
Advertising
Configuration
8200SHB0199
7-52
7.5.14.1 Level inversion for digital inputs
Only “HVAC” controllers
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C114
¤ Signal level digital
inputs
-0-
E4
E3
E2
E1
-0-
0
0
0
0
-1-
0
0
0
1
-2-
0
0
1
0
-3-
0
0
1
1
-4-
0
1
0
0
-5-
0
1
0
1
-6-
0
1
1
0
-7-
0
1
1
1
-8-
1
0
0
0
-9-
1
0
0
1
-10-
1
0
1
0
-11-
1
0
1
1
-12-
1
1
0
0
-13-
1
1
0
1
-14-
1
1
1
0
-15-
1
1
1
1
0: Ex is not inverted
1: Ex is inverted
Function
The levels of the digital inputs E1 ... E4 can be adapted according to the available signal levels.
Adjustment
Example
Task:
-
Terminal configuration C007 = -0- is set.
-
The DC-injection brake is to be activated via a LOW level at terminal E3.
Solution:
-
Set level inversion C114 = -4-.
- Terminal E3 reacts on LOW level, the DCB is activated.