Configuration – Lenze 8200 Frequency inverters User Manual

Page 167

Advertising
background image

Configuration

8200SHB0199

7-30

Function C144

-

C144 = -0-
- With chopper frequencies of 12 kHz or 16 kHz and if the max. permissible heat sink

temperature is exceeded (

J

max

) because of higher losses, the inverter will be inhibited, TRIP

will be indicated and the motors idles.

-

C144 = -1- (automatic chopper frequency derating):
- With chopper frequencies of 12 kHz or 16 kHz, the inverter reduces the chopper frequency

automatically to 8 kHz and thus ensures operation, if a heat-sink temperature of

J

max

-10

•C is

exceeded.

- After the heat sink has cooled down, the chopper frequency is automatically increased again.

Important

-

The automatic chopper frequency reduction leads to a higher noise generation compared to the
operation with 12 kHz or 16 kHz.

-

The current limitation C022/C023 is not automatically influenced by the selected chopper
frequency.

-

For 822X/824X only if C144 = -1-
- With chopper frequencies of 8 kHz, 12 kHz or 16 kHz, the controller reduces the chopper

frequency automatically to 4 kHz, if the maximum current is exceeded.