Configuration

8200SHB0199

7-67

Relay output K2

Setting range 820X/821X: K2 not available.

Setting range 822X/824X:

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C117

¤ Function relay K2

-1-

-0-

Ready for operation

-1-

TRIP fault message

-2-

Motor is running

-3-

Motor is running / CW rotation

-4-

Motor is running / CCW rotation

-5-

Field frequency f

d

= 0

-6-

f

dset

reached

-7-

Q

min

reached

-8-

I

max

reached

-9-

Overtemperature (

J

max

-10

•C)

-10-

TRIP or Q

min

or IMP

822X/824X

-11-

PTC warning

HVAC only

-12-

Apparent motor current
(C054) < threshold C156

-13-

Apparent motor current
(C054) < current threshold C156
and f

d

> Q

min

threshold (C017)

-14-

Apparent motor current
(C054) < threshold C156 and input
of ramp function generator = output
of ramp function generator

HVAC only

HVAC only

HVAC only

822X/824X

-15-

Warning motor phase failure

HVAC only

-16-

f

d

(C050) < f

dmin

(C010)

HVAC only

C054* Motor current

HVAC only

Display only

C156* Current threshold

0

0

{1 %}

150 HVAC only

Function

Series “HVAC”:

The changeover contact of relay K2 - terminals K21, K22, K24 - can be assigned with different
function to monitor the drive.

C008 = -12-, -13-, -14-:

-

The display value (C054) is smoothened with a ring memory with 500 ms.

-

The value set under C156 corresponds to a percentage of the rated controller current [I

r

].

-

With the control mode “Square characteristic” (C014 = 3), C156 is internally adapted via the field
frequency (C011):

C156

internal

[%]

C156 [%]ô

fd

2

[Hz

2

]

C011

2

[Hz

2

]

For instance, a belt monitoring can be implemented with this function extension.

Important

C156 is only stored in PAR1.