Network of several drives

8200SHB0199

10-2

10.2

Conditions for trouble-free network operation

Stop!

-

The installation and assembly notes must be applied (chapter 4).

-

Connect controllers only when they have similar DC-bus/mains-voltage
ranges (see the following table).

-

Adapt the thresholds of brake units and input and feedback modules.

-

All supplies should only be operated with the prescribed mains
chokes/mains filters! (See page 10-11)

10.2.1

Possible combinations

Possible combinations of Lenze controllers in DC-bus connection:

Type

Data

820X

821X

822X

824X

93XX

820X

**)

1 / N / PE / AC / 190 ... 260 V

á0 %/ 50 Hz/60 Hz

270 V ... 360 V

375 V

821X

3 / PE / AC / 320 ... 510 V

á0 %/ 50 Hz/60 Hz

450 V ... 715 V

725 V

*)

822X

3 / PE / AC / 320 ... 528 V

á0 %/ 50 Hz/60 Hz

460 V ... 740 V

725/765 V

*)

824X

3 / PE / AC / 320 ... 528 V

á0 %/ 50 Hz/60 Hz

460 V ... 740 V

725/765 V

*)

93XX

3 / PE / AC / 320 ... 528 V

á0 %/ 50 Hz/60 Hz

460 V ... 740 V

725/765 V

*)

Max. permissible mains-voltage range

DC-bus voltage range

Operating threshold - brake unit

*)

Set the thresholds of all units connected to the DC-bus to the same value.
Procedure: See the corresponding Operating Instructions.

**)

Central supply only possible from a DC source