3 parameter level, 3 change and store parameters, Parameter level – Lenze 8200 Frequency inverters User Manual

Page 142: Change and store parameters, Configuration

Advertising
background image

Configuration

8200SHB0199

7-5

7.2.3

Parameter level

-

The parameter level contains two parameter sets, PAR1 and PAR2. Press
the key SH to change from PAR1 to PAR2.

-

Each code provides parameters which can be used for drive adjustment.

- The blinking of PAR1 or PAR2 indicates in which parameter set you are.

-

There are four different parameter types:

- Absolute physical values

(e.g. 400 V, 10 s)

- Relative physical values

(e.g. 50 % setpoint)

- Numbers for certain states

(e.g. -0- = controller inhibited, -1- = controller enabled)

- Display values

These values can be displayed but not changed.
(e.g. motor-current).

-

Absolute and relative values can be modified in discrete steps. The steps
can change in the parameter-setting range.
Example: Acceleration time T

ir

(C012):

3 steps in the whole parameter setting range

- T

ir

of 0.0 2 s ... 1 s (step 0.02 s, with 820X step 0.05 s)

- T

ir

of 1 s ... 10 s (step 0.1 s)

- T

ir

of 10 s ... 100 s (step 1 s)

7.3

Change and store parameters

Each code with parameters which can be changed is factory set. There are three
possibilities, depending on the code, to change a parameter:

Labelling in code table

Acceptance and storage without acknowledgement

Cxxx

Acceptance and storage acknowledged with SH + PRG

Cxxx

¤

Acceptance and storage acknowledged with SH + PRG at controller inhibit

[Cxxx]

-

Parameters can be changed when the controller is enabled.

-

Changes of the operating parameters are accepted ONLINE.

-

Parameters, which influence the initialisation of the controller, must be
acknowledged with SH+PRG.

Note!

Overwriting of the parameter sets (C002) is only possible when the controller is
inhibited.