Configuration

8200SHB0199

7-41

Only series “HVAC”:

Adjustment

Scaling factor of the analog channel via C027:

-

C027 = 0.0 % ... 200.0 %
- Set-value input

-

C027 = -200.0 % ... -0.1%
- Inverse setpoint input

Offset adjustment of the analog channel via C026:
The adjustment of -10.00 V ... + 10.00 V refers to an input voltage of 10 V.

Setpoint input

Inverse setpoint input

C034 = -0-, C027 > 0 %
Offset adjustment via C026

C034 = -0-, C027 < 0 %
Offset adjustment via C026

fd

fd

max

C011

C027 0.0 % ... 200.0 %

C026

C027

0 %

100

%

200

%

Kl. 8

10 V

5 V
20 mA

fd

min

C010

fd

fd

max

C011

C027 -200.0 % ... -0.1 %

C026

C027

-100

%

-200

%

0 %

Kl. 8

10 V

5 V
20 mA

fd

min

C010

Calibration when using a
PID controller

If, for instance, the control range of a pressure control (C0005 = -6-) is to be limited to a value
lower than the rated sensor value, the effective pressure setpoint can be proportionally reduced
under C0027.
Example:

-

Pressure sensor 0 - 200 mbar (= P

r

) at E1.

-

Analog input of the pressure setpoint via terminal 8.

-

The max. pressure is to be limited to 120 mbar under C0027:

C0027

P

1

P

r

ô 100 %

120 mbar
200 mbar

ô 100 % 60 %

Important

-

With C026 < 0 V, f

dmin

can fall below the value set under C010.

-

With C005 = -0-, C026 and C027 are not active.

-

C026 and C027 are only stored in parameter set 1.

-

For terminal configurations with manual/remote changeover (C007 = -23- ... -27-):
- Change between motor potentiometer and manual/remote changeover via terminal (E1 ... E4).

-

For terminal configurations with manual/remote changeover (C007 = -23- ... -27-, -46-) and the
control mode LECOM (C001 = -3-):
- Change between setpoint via master current (C046, process setpoint) and setpoint input

possible via terminal (E1 ... E4).