Network of several drives

8200SHB0199

10-6

10.2.4

Fuses and cable cross-sections for a network of several
drives

The table values are valid for the operation of 821X/822X/824X controller in
DC-bus operation with PDC100 %, i.e. use of the max. rated controller power on
the DC-bus level (see page 10-10).

For operation with reduced power, it is possible to select smaller fuses and cable
cross-sections.

Type

821X/822X/824X:

Mains input L1, L2, L3, PE

DC input + V

DC

, -V

DC

, PE

Type

Operation with mains filter/mains choke

Fuse
F1, F2, F3

E.l.c.b.

Cable cross-section

1)

Fuse
F4, F5

Cable cross-section

1)

VDE

UL

VDE

mm

2

AWG

mm

2

AWG

8211 M 6A

-

B 6A

1

17

6.3A

1

17

8212 M 6A

-

B 6A

1

17

6.3A

1

17

8213 M 10A

-

B 10A

1.5

15

12A

1.5

15

8214 M 10A

-

B 10A

1.5

15

12A

1.5

15

8215 M 16A

-

B 13A

2.5

13

16A

2.5

13

8216 M 16A

-

B 16A

2.5

13

20A

4

11

8217 M 32A

-

B 32A

6

10

40A

6

10

8218 M 32A

-

B 32A

6

10

40A

6

10

8221 M 50A

50A

-

16

5

80A

16

7

8222 M 80A

80A

-

25

3

100A

25

5

8223 M 80A

80A

-

25

3

100A

25

3

8224 M 125A

125A

-

70

2/0

2x 100A

2)

2x 25 (1x 70)

2x 3 (1x 2/0)

8225 M 125A

125A

-

70

2/0

2x 100A

2)

2x 25 (1x 70)

2x 3 (1x 2/0)

8226 M 160A

175A

-

95

3/0

3x 80A

2)

3x 16 (1x 95)

3x 5 (1x 3/0)

8227 M 200A

200A

-

120

4/0

3x 100A

2)

3x 25 (1x 120) 3x 3 (1x 4/0)

8241 M 6A

5A

B 6A

1

17

6.3A

1

17

8242 M 6A

5A

B 6A

1

17

6.3A

1

17

8243 M 10A

10A

B 10A

1.5

15

12A

1.5

15

8244 M 10A

10A

B 10A

1.5

15

12A

1.5

15

8245 M 16A

20A

B 16A

2.5

13

20A

4

11

8246 M 32A

25A

B 32A

6

10

40A

6

10

1)

Observe national and regional regulations (e.g. VDE/EVU)!

2)

F4, F5 are possible because of parallel fuse connection.
Parallel connection cables can be used accordingly.