Network of several drives

8200SHB0199

10-4

10.2.3

DC-bus connection

-

Use short cable connections to the shared DC-bus star point.

-

Cross-section of the DC-bus connection cable

á

U

G

DC-bus

- must be selected according to the fuses F1 ... F3 of the corresponding

controller and the local conditions.

-

Cable cross-section of the DC-bus

- must be selected according to the sum of the mains supplies in the

DC-bus (see chapter 10.2.4).

-

Example:

Controller 1

Controler 2

Controller 3

F4, F5

3 AC / PE / xxx V / xx Hz

F1 ... F3

3 x 16A

3 x 50A

3 x 125A

Mains

DC bus

M

M

M

FIG 10-1

Example for the rating of the cable cross-section of the DC-bus

- Sum of the possible permanent r.m.s. currents of the parallel mains

supplies: 16 A + 50 A + 125 A = 191 A

- The cable cross-section is selected according to the resulting current of

191 A and the local conditions, as for instance, ambient temperature,
conductor material, conductor type, type of laying, expansion, standards,
and regulations.

-

Ensure smallest possible line inductivity by selecting the corresponding type
of installation:

- DC-bus star point in control cabinet above parallel busbar.

- Cables between controller (connections +U

G

and -U

G

) and DC-bus start

point must be in parallel or twisted.