3 single drives with 120 %overload, Single drives with 120 % overload, Technical data – Lenze 8200 Frequency inverters User Manual

Page 55: 3 single drives with 120 % overload

Advertising
background image

Technical Data

8200SHB0199

3-23

3.6.3

Single drives with 120 % overload

The table values are valid for operation of 82XX controllers with matching motor
and 120 % overload in pump and fan drives.

Type

Mains input L1, L2, L3, PE / motor connection U, V, W, PE

Type

Operation with mains filter/mains choke

Fuse F1, F2, F3

E.l.c.b.

Cable cross-section

1)

VDE

UL

VDE

mm

2

AWG

8211

M 6A

-

B 6A

1

17

8212

M 6A

-

B 6A

1

17

8213

M 10A

-

B 10A

1.5

15

8214

M 10A

-

B 10A

1.5

15

8215

M 20A

-

B 20A

4

11

8216

M 20A

-

B 20A

4

11

8217

M 32A

-

B 32A

6

10

8218

M 32A

-

B 32A

6

10

Type

Mains input L1, L2, L3, PE / motor connection U, V, W, PE

Type

Operation only with mains filter/mains choke

Fuse F1, F2, F3

E.l.c.b.

Cable cross-section

1)

VDE

UL

VDE

mm

2

AWG

8221

M 50A

50A

--

16

5

8222

M 63A

63A

--

25

3

8223

M 80A

80A

--

25

3

8224

M 125A

125A

--

70

2 / 0

8225

M 160A

175A

--

95

3 / 0

8226

M 160A

175A

--

95

3 / 0

8227

M 200A

200A

--

120

4 / 0

8241

M 6A

5A

B 6A

1

17

8242

M 6A

5A

B 6A

1

17

8243

M 10A

10A

B 10A

1.5

15

8244

M 10A

10A

B 10A

1.5

15

8245

M 20A

20A

B 20A

4

11

8246

M 32A

25A

B 32A

6

10

1)

Observe national and regional regulations (e.g. VDE/EVU)!