Configuration

8200SHB0199

7-63

7.6.3

Normalisation of an application datum

820X setting range: This function is not available.

Setting range 821X/822X/824X:

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C500* Display factor

Application datum
numerator

821X/822X/824X

2000

1

{1}

25000

C501* Display factor for

process variable
denominator

821X/822X/824X

10

1

{1}

25000

Function

-

Adaptation of field-frequency related parameters
C010, C011, C017, C019, C037, C038, C039, C050, or
C010, C011, C017, C019, C037, C038, C039, C046, C049, C050, C051, C181, C625, C626,
C627 (series “HVAC”)
to an application datum to be controlled, e.g. pressure, temperature, flow rate, humidity or speed.

-

The normalisation implements an absolute or relative selection of an application datum.

-

All codes indicated are normalised at the same time.

Adjustment

The display value is calculated from:

CXXX

C011

200 ô

C500
C501

Example

The speed setpoint is to be input and displayed as relative or absolute value.
Values: P

set

= 5 bar, if f

dmax

= 50 Hz (C011)

a) Relative normalisation in %

100.00 (%)

50

200 ô

4000

10

e.g. C500 = 4000, C501 = 10

b) Absolute normalisation in physical units

5.00 (bar)

50

200 ô

200

10

e.g. C500 = 200; C501 = 10

Important

-

All codes indicated above are normalised at the same time.

-

After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501.